2UD, 2UDF & 2UDCP Two Door Disconnect Enclosures - NEMA 12
Selection Guide |
<< Product Information << Disconnect Enclosures <<
|
| |
| Operator Adaptor Kits |
| Part No. |
Operator Make & Type |
| AKU |
ABB Controls operating handle |
|
Disconnect Switch |
DSFHN-HS12 |
|
Circuit Breaker |
K7FHD-HS12 |
|
Allen Bradley 1494V variable depth operating handle |
|
Disconnect Switch |
|
|
30-200 |
1494V H1 |
|
Circuit breaker |
1494V H11 |
|
Cutler Hammer operating handle |
|
|
Disconnect Switch |
C361H1 or H3 |
|
Circuit Breaker |
|
|
|
150 amps |
C371H1 or H3 |
|
|
250 to 600 amps |
C371H5 or H7 |
|
Circuit Breaker C371 Flex-Shaft™ handle mechanism. |
|
General Electric operating handle |
|
Disconnect Switch |
STDA1or STDA2 |
|
Circuit Breaker |
STDA1or STDA2 |
|
Circuit Breaker Spectra-Flex™ cable operators |
|
|
150 to 600 amps |
STDA1 |
|
|
SK1200 |
STDA3 |
|
Siemens I-T-E Max-Flex™ operating handle |
|
Disconnect Switch, Variable depth |
FHOHS |
|
Circuit Breaker |
|
|
125 to 600 |
FHOH |
|
800 to 2000 |
FHOHN |
|
Square D class 9422 operating mechanism |
|
Disconnect Switch variable depth |
9422 type A1 |
|
Circuit Breaker variable depth |
9422 type A1 |
|
Disconnect Switch with cable mechanism |
9422 type A1 |
|
Circuit Breaker with cable mechanism |
9422 type A1 |
| AK1494FD |
Allen Bradley |
1494F and D |
| BPAK |
Blank Adapter Plate |
|
|
| |
Space Occupied by Disconnects
|
Note: Disconnects will occupy space on panel shown by dimensions "K", "L", and M". Wiring space "P" is available when disconnect is installed in the enclosure.
*The disconnect information and space occupied tables based on data supplied by disconnect manufacturer’s bulletins. Hammond Manufacturing not responsible for dimensional accuracy. |
 |
|
- All Universal series enclosures require one adaptor kit (ordered separately) to adapt the type of disconnect and mechanism to be used.
- Each brand and type requires a different adaptor kit.
- Each kit contains an adaptor plate and master door interlocking mechanism.
- Fully detailed, illustrated instructions included.
|
|
|
| |
| ABB Controls |
| Disconnect switch: |
- Flange operated switch (fusible or non-fusible)
- Shaft:
- 12.13" deep enclosures use
DSFHS-12
- 18.13" deep enclosures use
DSFHS-17
- 24.13" deep enclosures, platform must be used with shaft (not included)
- Handle: DSFHN-HS12
|
| |
| Circuit breaker: |
- Circuit breaker: ABB
- Operating mechanism
- Shaft:
- 12.13" deep enclosures use
K7FHD-S12
- 18.13" deep enclosures use
K7FHD-S17
- 24.13" deep enclosures, platform must be used with shaft (not included)
- Handle mechanism: K7FHD-HS12
|
| |
| Allen Bradley |
| Bulletin 1494F flange mounted disconnect switch: |
- Disconnect switch
Fuse block adaptor (if required)
- Line and load connectors (if required)
|
| |
1494D flange mounted circuit breaker operating mechanism, order:
|
- Circuit breaker: C-H Westinghouse
- Operating mechanism
- Slide mechanism
|
| |
Bulletin 1494V flange mounted disconnect switch, order:
|
- Disconnect switch
- Operating handle
- Connecting rod (long)
- Trailer fuse block kit (if required)
- Fuse kit (if required)
- Line and load connectors (if required)
|
| |
| Bulletin 1494V flange mounted circuit breaker operating mechanism, order: |
- Circuit breaker: C-H Westinghouse
- Operating mechanism
- Operating handle
- Connecting rod (long)
- When Allen Bradley 1494V devices are installed in 72" high enclosures with the operating handle mounted on the center post, an optional Allen Bradley channel support kit is recommended.
|
|
| C-H Westinghouse |
| Type C361 disconnect switch: |
- Disconnect switch with an operating mechanism
- Operating handle: C361H1 or C361H3
- In 24.13" deep enclosures, platform must be used with shaft (not included)
|
| |
| Type C371 circuit breaker operating mechanism with a C-H Westinghouse circuit breaker: |
- Circuit breaker
- Operating mechanism
- Long operating rod (if required)
- Operating handle:
- 150 amp - C371H1 or C371H3
- 250 through 600 amp - C371H5 or C371H7
|
| |
| Flex-Shaft™ handle mechanism: |
- Circuit breaker
- Complete Flex-Shaft™ handle mechanism
|
| |
| General Electric |
| Disconnect switch: |
- Disconnect switch: Type QMR or QMW
- Fuse clip kit or no-fuse kit
- Flange handle: STDA1 or STDA2
- Variable depth operating mechanism
- Extended length drive rod (if required)
|
| |
| Circuit breaker: |
- Circuit breaker
- Flange handle: STDA1 or STDA2
- Variable depth operating mechanism
- Extended length drive rod (if required)
- An optional General Electric Flange Stiffener Kit (TDSR) is recommended when General Electric Type TDA devices are installed in 72.13" high enclosures with operating handle mounted on centerpost. Use with TDOM1, TDOM2, TDOM3, S100M1A, and S100M3 operating mechanisms.
|
| |
| Circuit breaker with a Spectra-Flex™ cable operator: |
- Circuit breaker
- Flange mounted handle mechanism:
- 150 to 600 amps - STDA1
- SK1200 - STDA3
- Breaker mounted mechanism
- Operating cable
|
|
| I-T-E Siemens |
| Disconnect switch: |
- Basic switch (right-hand)
- Fuse or no-fuse kit
- Flange mounted handle: FHOHS
- Switch operator
- Operating cable:
- FHOEC036 cable for 12.13" deep
- FHOECO48 for 18.13" and 24.13" deep enclosures
|
| |
| Circuit breaker: |
- Circuit breaker
- Pressure wire connectors
- Flange mounted handle:
- 100 to 600 - FHOH
- 800 to 2000 - FHOHN
- Circuit breaker operator mechanism
- Operating cable:
- 36" cable for 12.13" or 18.13" deep
- 48" for 24.13" deep enclosures
- These items are available from Siemens I-T-E as a complete mechanism with a 36" operating cable only Order items separately when using a 48" cable
|
| |
| Square D |
| Disconnect switch: |
- Disconnect switch with operating mechanism
- Universal handle mechanism: Type A-1
- Long operating rod (if required)
|
| |
| Circuit breaker: |
- Circuit breaker
- Operating mechanism
- Universal handle mechanism: Type A-1
- Long operating rod (if required)
|
| |
| Class 9422 Type T disconnect switch with a cable mechanism: |
- Disconnect switch with operating mechanism: Class 9422, Type T
- Handle mechanism: Class 9422, Type A-1
- Cable mechanism: Class 9422 CFT_O, 3, 5, or 10 foot
|
| |
| Circuit breaker with a cable mechanism: |
- Circuit breaker: Square D
- Handle mechanism: Class 9422, type A-1
- Cable mechanism: Class 9422 CFT_O, 3, 5, or 10 foot
- An optional Square D Channel flange Support Kit (9422-C1) is recommended when some Square D devices are installed in 72.13" high enclosures with operating handle mounted on centerpost.
|
|
|
| |
| ABB Controls
ABB Controls Disconnect Switches (Flange Mounted Operators)
|
| Fits Enclosure Height |
ABB Switch
Number |
Amp |
|
|
|
Space
Occupied |
|
When
A=60.13
P |
When
A=72.13
P |
| 60.13 |
72.13 |
Rating |
Fuse Clip |
Fuse Class |
L |
M |
N |
| • |
• |
OETL-NF30-F |
30A |
No Fuse |
— |
4.45 |
3.91 |
0.25 |
9.53 |
15.53 |
| • |
• |
OETL-NF60-F |
60A |
No Fuse |
— |
4.86 |
3.91 |
0.25 |
9.34 |
15.34 |
| • |
• |
OETL-NF100-F |
100A |
No Fuse |
— |
4.86 |
4.91 |
0.25 |
8.78 |
14.78 |
| • |
• |
OETL-NF175-F |
175A |
No Fuse |
— |
7.30 |
6.62 |
0.25 |
6.53 |
12.53 |
| • |
• |
OETL-NF200-F |
200A |
No Fuse |
— |
7.36 |
7.41 |
0.25 |
6.53 |
12.53 |
| • |
• |
OESA-F30J6-F |
30A |
30A-600V |
J |
4.28 |
6.70 |
0.25 |
7.85 |
13.86 |
| • |
• |
OESA-F60J6-F |
60A |
60A-600V |
J |
4.28 |
6.39 |
0.25 |
7.85 |
13.86 |
| • |
• |
OESA-F100J6-F |
100A |
100A-600V |
J¹ |
6.54 |
7.78 |
0.25 |
7.42 |
13.42 |
|
|
|
200A² |
|
|
|
|
|
|
|
¹ J type fuse clips are standard. If 600 V Type “T” fuse clips are desired order T type fuse adaptor kit.
² 200 A available by using non-fusible 200A switch and a trailing fuse block. (consult ABB) |
| |
| ABB Controls Circuit Breaker (Flange Mounted Operators) |
| Fits Enclosure Height |
ISOMAX Circuit
Breaker |
Amp
Rating |
Operating
Mechanism |
Frame
Type |
Space Occupied |
|
When
A=60.13
P |
When
A=72.13
P |
| 60.13 |
72.13 |
L |
M |
N |
| • |
• |
S1N100TL |
100A |
K2FHD-M |
S1 |
5.30 |
4.60 |
0.63 |
8.33 |
14.33 |
| • |
• |
S3N150TW |
150A |
K3FHD-M |
S3 |
6.67 |
5.02 |
0.63 |
7.73 |
13.73 |
| • |
• |
S3N225TW |
225A |
K3FHD-M |
S3 |
6.67 |
5.02 |
0.63 |
7.73 |
13.73 |
| • |
• |
S4N250BW |
250A |
K4FHD-M |
S4 |
8.45 |
5.02 |
0.63 |
6.20 |
12.20 |
| • |
• |
S5N400TW |
400A |
K5FHD-M |
S5 |
8.45 |
6.40 |
0.63 |
6.20 |
12.20 |
| • |
• |
S6N600TW |
600A |
K6FHD-M |
S6 |
8.33 |
10.00 |
0.63 |
5.53 |
11.53 |
| • |
• |
S6N800TW |
800A |
K6FHD-M |
S6 |
8.33 |
10.00 |
0.63 |
5.53 |
11.53 |
|
"K" = 7.88 when "A" = 60.13
"K" = 13.88 when "A" = 72.13 |
| Charts reference Space Occupied by Disconnect Drawing. |
| |
Allen Bradley
Allen Bradley 1494F Disconnect Switches |
| Fits Enclosure Height |
ABB Switch
Number |
Amp
Rating |
|
|
|
Space
Occupied
M¹ |
|
When
A=60.13
P |
When
A=72.13
P |
| 60.13 |
72.13 |
Fuse Clip |
Fuse Class |
L |
N |
| • |
• |
N30 |
30A |
No Fuse |
— |
4.62 |
6.50 |
0.63 |
5.31 |
11.31 |
| • |
• |
NF30 |
30A |
30A-250V |
H, K, R |
6.50 |
6.50 |
0.63 |
5.31 |
11.31 |
| • |
• |
NF30 |
30A |
60A-250V |
H, K, R |
7.25 |
6.50 |
0.63 |
5.31 |
11.31 |
| • |
• |
NF30 |
30A |
30A-600V |
H, K, R |
9.25 |
6.50 |
0.63 |
5.31 |
11.31 |
| • |
• |
NF30 |
30A |
60A-600V |
H, K, R |
9.75 |
6.50 |
0.63 |
5.31 |
11.31 |
| • |
• |
NF30 |
30A |
30A-600V |
J |
6.50 |
6.50 |
0.63 |
5.31 |
11.31 |
| • |
• |
NF30 |
30A |
60A-600V |
J |
6.62 |
6.50 |
0.63 |
5.31 |
11.31 |
| • |
• |
N60 |
60A |
No Fuse |
— |
4.62 |
6.50 |
0.63 |
4.62 |
10.62 |
| • |
• |
NF60 |
60A |
30A-600V |
H, K, R |
10.38 |
6.50 |
0.63 |
4.62 |
10.62 |
| • |
• |
NF60 |
60A |
60A-250V |
H, K, R |
8.38 |
6.50 |
0.63 |
4.62 |
10.62 |
| • |
• |
NF60 |
60A |
100A-250V |
H, K, R |
10.88 |
6.50 |
0.63 |
4.62 |
10.62 |
| • |
• |
NF60 |
60A |
60A-600V |
H, K, R |
10.88 |
6.50 |
0.63 |
4.62 |
10.62 |
| • |
• |
NF60 |
60A |
100A-600V |
H, K, R |
12.88 |
6.62 |
0.63 |
4.62 |
10.62 |
| • |
• |
NF60 |
60A |
60A-600V |
J |
7.75 |
6.50 |
0.63 |
4.62 |
10.62 |
| • |
• |
NF60 |
60A |
100A-600V |
J |
9.75 |
6.50 |
0.63 |
4.62 |
10.62 |
|
• |
N100 |
100A |
No Fuse |
— |
4.62 |
7.25 |
0.63 |
— |
8.75 |
|
• |
NF100 |
100A |
100A-250V |
H, K, R |
11.38 |
7.38 |
0.63 |
— |
8.75 |
|
• |
NF100 |
100A |
200A-250V |
H, K, R |
12.25 |
7.62 |
0.63 |
— |
8.75 |
|
• |
NF100 |
100A |
100A-600V |
H, K, R |
13.38 |
7.50 |
0.63 |
— |
8.75 |
|
• |
NF100 |
100A |
200A-600V |
H, K, R |
14.75 |
7.75 |
0.63 |
— |
8.75 |
|
• |
NF100 |
100A |
100A-600V |
J |
10.12 |
7.38 |
0.63 |
— |
8.75 |
|
• |
NF100 |
100A |
200A-600V |
J |
10.88 |
7.50 |
0.63 |
— |
8.75 |
|
• |
N200 |
200A |
No Fuse |
— |
7.12 |
10.38 |
0.56 |
— |
7.13 |
|
• |
NF200 |
200A |
200A-250V |
H, K, R |
15.00 |
10.38 |
0.56 |
— |
7.13 |
|
• |
NF200 |
200A |
400A-250V |
H, K, R |
16.56 |
10.75 |
0.56 |
— |
7.13 |
|
• |
NF200 |
200A |
200A-600V |
H, K, R |
17.56 |
10.38 |
0.56 |
— |
7.13 |
|
• |
NF200 |
200A |
400A-600V |
H, K, R |
19.56 |
11.00 |
0.56 |
— |
7.13 |
|
• |
NF200 |
200A |
200A-600V |
J |
13.69 |
10.38 |
0.56 |
— |
7.13 |
|
• |
NF200 |
200A |
400A-600V |
J |
15.00 |
10.62 |
0.56 |
— |
7.13 |
¹"M" dimension does not allow for auxiliary switches. Refer to Allen Bradley instructions if additional space is required. |
| |
| Allen Bradley 1494D Operators (Circuit Breakers) |
| Fits Enclosure Height |
Alan Bradley
Type Number |
Amp
Rating |
Circuit Breker Type |
|
Space
Occupied |
|
When
A=60.13
P |
When
A=72.13
P |
| 60.13 |
72.13 |
L |
M¹ |
N |
| • |
• |
N4/N40 |
150A |
C-H Westinghouse
EHD,FD,FDB,FDC,HFD,HMCP |
5.81 |
4.56 |
0.63 |
5.25 |
11.25 |
| • |
• |
N5/N55 |
225A |
General Electric
TFK, THFK, TFC |
8.81 |
4.75 |
0.63 |
4.44 |
10.44 |
| • |
• |
N5/N50 |
250A |
C-H Westinghouse
JD,JDB,JDC,HJD,HMCP |
8.81 |
4.75 |
0.63 |
4.44 |
10.44 |
|
• |
N5/N60 |
400A |
C-H Westinghouse
KD,KDB,DK,HKD,HMCP |
8.81 |
5.88 |
0.63 |
— |
10.50 |
1 "M" dimension does not allow for auxiliary switches. Refer to Allen Bradley instructions if additional space is required.
"K" = 5.88 when "A" = 60.13
"K" = 11.88 when "A" = 72.13 (except 200A switches)
"K" = 10.56 when "A" = 72.13 (200A switches only).
|
| |
| Allen Bradley 1494V Operators (Disconnect Switches) |
| Fits Enclosure Height |
ABB Switch
Number |
Amp |
|
|
|
Space
Occupied |
|
When
A=60.13
P |
When
A=72.13
P |
| 60.13 |
72.13 |
Rating |
Fuse Clip |
Fuse Class |
L |
M² |
N |
| • |
• |
DS30 |
30A |
No Fuse |
— |
3.88 |
6.75 |
1.06 |
6.00 |
12.00 |
| • |
• |
DS30 |
30A |
30A-250V |
H,K,R |
5.25 |
6.75 |
1.06 |
6.00 |
12.00 |
| • |
• |
DS30 |
30A |
30A-600V |
H,K,R |
8.00 |
6.75 |
1.06 |
6.00 |
12.00 |
| • |
• |
DS30 |
30A |
30A-600V |
J |
5.25 |
6.75 |
1.06 |
6.00 |
12.00 |
| • |
• |
DS30 |
30A |
60A-250V |
H,K |
6.00 |
6.75 |
1.06 |
6.00 |
12.00 |
| • |
• |
DS30 |
30A |
60A-600V |
H,K |
8.50 |
6.75 |
1.06 |
6.00 |
12.00 |
| • |
• |
DS30 |
30A |
60A-600V |
J |
5.38 |
6.75 |
1.06 |
6.00 |
12.00 |
| • |
• |
DS60 |
60A |
No Fuse |
— |
3.88 |
6.75 |
1.06 |
5.81 |
11.81 |
| • |
• |
DS60 |
60A |
60A-250V |
H,K,R |
6.00 |
6.75 |
1.06 |
5.81 |
11.81 |
| • |
• |
DS60 |
60A |
60A-600V |
H,K,R |
8.50 |
6.75 |
1.06 |
5.81 |
11.81 |
| • |
• |
DS60 |
60A |
60A-600V |
J |
5.38 |
6.75 |
1.06 |
5.81 |
11.81 |
| • |
• |
DS60 |
60A |
30A-600V |
H,K,R |
8.00 |
6.75 |
1.06 |
5.81 |
11.81 |
| • |
• |
DS60 |
60A |
100A-250V |
H,K |
8.50 |
6.75 |
1.06 |
5.81 |
11.81 |
| • |
• |
DS60 |
60A |
100A-600V |
H,K |
10.50 |
6.75 |
1.06 |
5.81 |
11.81 |
| • |
• |
DS60 |
60A |
100A-600V |
J |
7.25 |
6.75 |
1.06 |
5.81 |
11.81 |
| • |
• |
DS100¹ |
100A |
No Fuse |
— |
3.88 |
6.75 |
1.06 |
5.81 |
11.81 |
| • |
• |
DS100¹ |
100A |
100A-250V |
H,K,R |
8.12 |
6.75 |
1.06 |
5.81 |
11.81 |
| • |
• |
DS100¹ |
100A |
100A-600V |
H,K,R |
10.12 |
6.75 |
1.06 |
5.81 |
11.81 |
| • |
• |
DS100¹ |
100A |
100A-600V |
J |
6.80 |
6.75 |
1.06 |
5.81 |
11.81 |
| • |
• |
DS100¹ |
100A |
60A-600V |
H,K,R |
10.12 |
6.75 |
1.06 |
5.81 |
11.81 |
| • |
• |
DS100¹ |
100A |
60A-600V |
J |
8.88 |
6.75 |
1.06 |
5.81 |
11.81 |
|
• |
DS2001 |
200A |
No Fuse |
— |
4.75 |
8.00 |
1.06 |
— |
10.34 |
|
• |
DS2001 |
200A |
200A-250V |
H,K,R |
10.88 |
8.00 |
1.06 |
— |
10.34 |
|
• |
DS2001 |
200A |
200A-600V |
H,K,R |
13.88 |
8.00 |
1.06 |
— |
10.34 |
|
• |
DS2001 |
200A |
200A-600V |
J |
9.50 |
8.00 |
1.06 |
— |
10.34 |
|
• |
DS2001 |
200A |
100A-600V |
H,K,R |
12.00 |
8.00 |
1.06 |
— |
10.34 |
|
• |
DS2001 |
200A |
100A-600V |
J |
8.75 |
8.00 |
1.06 |
— |
10.34 |
1 Series B
2 "M" dimension does not allow for auxiliary switches |
| |
| Allen Bradley 1494V Operators (Circuit Breakers) |
| Fits Enclosure Height |
Alan Bradley
Type Number |
Amp |
|
|
Space
Occupied |
|
When
A=60.13
P |
When
A=72.13
P |
| 60.13 |
72.13 |
Rating |
Circuit Breker Type |
L |
M1 |
N |
| • |
• |
M40 |
15A-150A |
C-H Westinghouse
EHD,FD,FDB,FDC,HFD,HMCP |
5.00 |
4.62 |
1.06 |
7.25 |
13.25 |
| • |
• |
M50 |
70A-250A |
C-H Westinghouse
JD,JDB,JDC,HJD,HMCP |
9.75 |
4.88 |
1.06 |
6.81 |
12.81 |
|
• |
M60 |
100A-400A |
C-H Westinghouse
KD,KDB,DK,HKD,HMCP |
9.69 |
6.25 |
1.06 |
— |
12.62 |
1 "M" dimension does not allow for auxiliary switches. Refer to Allen Bradley instructions if additional space is required.
"K" = 7.88 when "A" = 60.13
"K" = 13.88 when "A" = 72.13 |
| |
Cutler Hammer
Cutler Hammer C361 Disconnect Switches |
| Fits Enclosure Height |
Cutler Hammer
Type Number |
Amp |
|
|
|
Space
Occupied |
|
When
A=60.13
P |
When
A=72.13
P |
| 60.13 |
72.13 |
Rating |
Fuse Clip |
Fuse Class |
L |
M |
N |
| • |
• |
C361NC |
30A |
No Fuse |
— |
5.75 |
7.55 |
0.63 |
6.50 |
12.50 |
| • |
• |
C361SC21 |
30A |
30A-250V |
H, K, R |
8.38 |
7.55 |
0.63 |
6.50 |
12.50 |
| • |
• |
C361SC61 |
30A |
60A-250V |
H, K, R |
8.38 |
7.55 |
0.63 |
6.50 |
12.50 |
| • |
• |
C361SC61 |
30A |
30A-600V |
H, J, K, R |
8.38 |
7.55 |
0.63 |
6.50 |
12.50 |
| • |
• |
C361ND |
60A |
No Fuse |
— |
5.75 |
7.55 |
0.63 |
6.50 |
12.50 |
| • |
• |
C361SD22 |
60A |
60A-250V |
H, K, R |
8.38 |
7.55 |
0.63 |
6.50 |
12.50 |
| • |
• |
C361SD22 |
60A |
30A-600V |
J |
8.38 |
7.55 |
0.63 |
6.50 |
12.50 |
| • |
• |
C361SD62 |
60A |
60A-600V |
H, K, R |
8.38 |
7.55 |
0.63 |
6.50 |
12.50 |
| • |
• |
C361SD62 |
60A |
60A-600V |
J |
8.38 |
7.55 |
0.63 |
6.50 |
12.50 |
| • |
• |
C361NE |
100A |
No Fuse |
— |
5.56 |
9.07 |
0.63 |
6.06 |
12.06 |
| • |
• |
C361SE263 |
100A |
100A-250V |
H, K, R |
10.31 |
9.07 |
0.63 |
6.06 |
12.06 |
| • |
• |
C361SE263 |
100A |
100A-600V |
H, K, R |
10.31 |
9.07 |
0.63 |
6.06 |
12.06 |
| • |
• |
C361SE263 |
100A |
100A-600V |
J |
10.31 |
9.07 |
0.63 |
6.06 |
12.06 |
| • |
• |
C361NF |
200A |
No Fuse |
— |
13.06 |
10.12 |
0.63 |
4.06 |
10.12 |
| • |
• |
C361SF264 |
200A |
200A-250V |
H, K, R |
13.06 |
10.12 |
0.63 |
4.06 |
10.12 |
| • |
• |
C361SF264 |
200A |
200A-600V |
H, K, R, J |
13.06 |
10.12 |
0.63 |
4.06 |
10.12 |
|
| |
| Cutler Hammer C371 Circuit Breaker (C-H Westinghouse Circuit Breakers) |
| Fits Enclosure Height |
Cutler Hammer
Mechanisms |
Amp |
|
|
Space Occupied |
|
When
A=60.13
P |
When
A=72.13
P |
| 60.13 |
72.13 |
Rating |
Frame Type |
L |
M |
N |
| • |
• |
C371E |
150A |
F Frame EHD,FDB,FD,HFD,FDC |
6.00 |
5.62 |
0.63 |
7.62 |
13.62 |
| • |
• |
C371E |
150A |
F Frame HMCP |
6.00 |
5.62 |
0.63 |
7.62 |
13.62 |
| ¹ |
• |
C371F |
250A |
J Frame JDB,JD,HJD,JDC |
8.94 |
8.12 |
0.63 |
7.50 |
13.50 |
| ¹ |
• |
C371F |
250A |
J Frame HMCP |
10.94 |
8.12 |
0.63 |
7.50 |
13.50 |
| ¹ |
• |
C371F |
400A |
K Frame DK,KDB,KD,HKD |
9.75 |
8.12 |
0.63 |
7.00 |
13.00 |
| ¹ |
• |
C371F |
400A |
K Frame HMCP |
9.75 |
8.12 |
0.63 |
7.00 |
13.00 |
|
² |
C371G |
600A |
L Frame LD,HLD,LDC |
8.44 |
12.00 |
0.63 |
- |
11.38 |
|
² |
C371G |
600A |
L Frame HMCP |
8.44 |
12.00 |
0.63 |
- |
11.38 |
1Wire bend space "P" does not allow cable size larger than 4/0 AWG in a 60.13" tall enclosures.
2Wire bend space "P" does not allow cable size larger than 300 MCM.
"K" = 7.88 when "A" = 60.13
"K" = 13.88 when "A" = 72.13
Charts reference Space Occupied by Disconnect Drawing.
|
| |
| Cutler Hammer Flex-Shaft™ Operator Mechanisms (C-H Westinghouse Circuit Breakers) |
| Complete Operator |
|
|
Breaker Height "X" |
Breaker Width "Y" |
| Mechanisms |
Amp Rating |
Frame Type |
(in inches) |
(in inches) |
| F1S03 |
150A |
F Frame EHD,FDB,FD,HFD |
6.00 |
4.12 |
| F1S03 |
150A |
F Frame HCMP |
6.00 |
4.12 |
| F2S03 |
250A |
J Frame JDB,JD,HJD,JDC |
10.00 |
4.12 |
| F2S03 |
250A |
J Frame HCMP |
10.00 |
4.12 |
| F3S03 |
400A |
K Frame DK,KDB,KD,HKD |
10.12 |
5.50 |
| F3S03 |
400A |
K Frame HCMP |
12.45 |
5.50 |
| F4S04 |
600A |
L Frame LD,HLD,LDC |
10.75 |
8.25 |
| F7S04 |
800A |
M Frame MD,MDS |
16.00 |
8.25 |
| F5S04 |
1200A |
N Frame ND,HND,NDC |
16.00 |
8.25 |
| F6S04 |
2500A |
R Frame RD,CRD, RDC |
16.00 |
15.50 |
Part numbers for Complete Operator Mechanisms include flange mounted handle, flexible shaft and circuit breaker mechanism.
The last digit of the part number denotes the shaft length (F1S03=3' length).
F,J,K frame Flex-Shafts™ available in 3' to 10' lengths.
L,N,R frame Flex-Shafts™ available in 4' to 6' lengths.
Space Occupied By Disconnect
1. Flex-Shaft™ System permits circuit breaker locations separate from flange mounted handle mechanism.
2. See National Electrical Code 2005 article 430-10(b) for wiring space (Ref "P") needed for line side conductors.
3. Select shaft length based on location of circuit breaker in the enclosure. Maintain a 4" minimum bending radius for the Flex-Shaft™.
4. Space occupied by circuit breaker is calculated by:
|
- Overall (Height "X" and Width "Y")
- Minimum wire bend space (manufacturer specified)
- Location "M" from right to left.
Charts reference Space Occupied by Disconnect Drawing |
|
| |
|
General Electric
General Electric Type STDA Disconnect Switche Operators |
|
| Fits Enclosure Height |
General Electric
Switch
Mechanisms |
Amp
Rating |
|
|
|
Space
Occupied
M |
|
When
A=60.13
P |
When
A=72.13
P |
| 60.13 |
72.13 |
Fuse Clip |
Fuse Class |
L |
N |
| • |
• |
TDOM1A |
30A |
No Fuse |
- |
6.88 |
5.38 |
0.63 |
8.38 |
14.38 |
| • |
• |
TDOM1A |
30A |
30A-250V |
H, R |
6.88 |
5.38 |
0.63 |
8.38 |
14.38 |
| • |
• |
TDOM1B |
30A |
30A-600V |
H, R |
11.5 |
5.38 |
0.63 |
8.38 |
14.38 |
| • |
• |
TDOM1B |
30A |
60A-250V |
H, R |
11.5 |
5.38 |
0.63 |
8.38 |
14.38 |
| • |
• |
TDOM1B |
30A |
60A-600V |
H, R |
11.5 |
5.38 |
0.63 |
8.38 |
14.38 |
| • |
• |
TDOM1A |
60A |
No Fuse |
- |
6.88 |
5.38 |
0.63 |
8.38 |
14.38 |
| • |
• |
TDOM1B |
60A |
60A-250V |
H, R |
11.5 |
5.38 |
0.63 |
8.38 |
14.38 |
| • |
• |
TDOM1B |
60A |
60A-600V |
H, R |
11.5 |
5.38 |
0.63 |
8.38 |
14.38 |
| • |
• |
TDOM1B |
60A |
100A-250V |
H, R |
11.5 |
5.38 |
0.63 |
8.38 |
14.38 |
| • |
• |
TDOM1B |
60A |
100A-600V |
H, R |
11.5 |
5.38 |
0.63 |
8.38 |
14.38 |
| • |
• |
TDOM1A |
100A |
No Fuse |
- |
6.88 |
5.38 |
0.63 |
8.38 |
14.38 |
| • |
• |
TDOM1B |
100A |
100A-250V |
H, R |
11.5 |
5.38 |
0.63 |
8.38 |
14.38 |
| • |
• |
TDOM1B |
100A |
100A-600V |
H, R |
11.5 |
5.38 |
0.63 |
8.38 |
14.38 |
| • |
• |
TDOM1B |
100A |
200A-250V |
H, R |
11.5 |
5.38 |
0.63 |
8.38 |
14.38 |
| • |
• |
TDOM1B |
100A |
200A-600V |
H, R |
11.5 |
5.38 |
0.63 |
8.38 |
14.38 |
| • |
• |
TDOM2 |
200A |
No Fuse |
- |
7 |
9.25 |
0.63 |
5.69 |
11.69 |
| • |
• |
TDOM2 |
200A |
200A-250V |
H, R |
15.38 |
9.25 |
0.63 |
5.69 |
11.69 |
| • |
• |
TDOM2 |
200A |
200A-600V |
H, R |
15.38 |
9.25 |
0.63 |
5.69 |
11.69 |
|
|
| |
|
| General Electric Type STDA Circuit Breaker Operators |
|
| Fits Enclosure Height |
General Electric
Circuit Breaker
Mechanisms |
Amp
Rating |
Frame Type |
|
Space Occupied |
When
A=60.13
P |
When
A=72.13
P |
| 60.13 |
72.13 |
L |
M |
N |
| • |
• |
TDOM1A |
150A |
TEB, TED, THED |
6.88 |
5.38 |
0.63 |
7.24 |
13.24 |
| • |
• |
TDOM1A |
150A |
TEC |
6.88 |
5.38 |
0.63 |
7.24 |
13.24 |
| • |
• |
TDOM1B |
150A |
TB1 |
11.50 |
5.38 |
0.63 |
7.24 |
13.24 |
| • |
• |
TDOM1B |
150A |
TEC, TECL |
11.50 |
5.38 |
0.63 |
7.24 |
13.24 |
| • |
• |
TDOM1C |
150A |
TEL |
6.88 |
5.38 |
0.63 |
7.24 |
13.24 |
| • |
• |
TDOM1D |
150A |
THLC1 |
6.88 |
5.38 |
0.63 |
5.87 |
11.87 |
| • |
• |
TDOM3 |
225A |
TFJ |
10.38 |
5.88 |
0.63 |
6.81 |
12.81 |
| • |
• |
TDOM3 |
225A |
TFK, THFK, TFL |
10.38 |
5.88 |
0.63 |
6.81 |
12.81 |
|
• |
TDOM4 |
400A |
TJJ, TJK4, THJK4, TJL4V |
8.25 |
9.50 |
0.63 |
— |
11.91 |
|
• |
TDOM4 |
600A |
TJK6, THJK6, TJ4V, TJL4V |
8.25 |
9.50 |
0.63 |
— |
11.91 |
|
• |
TDOM5 |
400A |
TB4, TJH6S |
14.25 |
9.50 |
0.63 |
— |
11.91 |
|
• |
TDOM6 |
225A |
TLB2, THLC2 |
11.75 |
9.50 |
0.63 |
— |
11.35 |
|
• |
TDOM6 |
400A |
TLB4, THLC4 |
11.75 |
9.50 |
0.63 |
— |
9.97 |
| • |
• |
SDOM1A |
150A |
SE150 |
6.88 |
5.38 |
0.63 |
7.24 |
13.24 |
| • |
• |
SDOM3 |
250A |
SPECTRA SF250 |
10.38 |
5.88 |
0.63 |
6.81 |
11.88 |
|
• |
SDOM4 |
600A |
SPECTRA SG600 |
10.00 |
7.12 |
0.63 |
— |
9.18 |
"K" = 7.88 when "A" = 60.13
"K" = 13.88 when "A" = 72.13 |
|
| |
|
| General Electric Circuit Breakers (Spectra-Flex™ Cable Operators) |
|
| Fits Enclosure Height |
|
|
Circuit Breaker Height |
Circuit Breaker Width |
| 60.13 |
72.13 |
Frame Size |
Max Amp Rating |
"X" |
"Y" |
| • |
• |
E150 |
150A |
6.31 |
4.12 |
| • |
• |
SE150 |
150A |
6.31 |
4.12 |
| • |
• |
SF250 |
250A |
10.12 |
4.12 |
| • |
• |
SG600 |
600A |
10.09 |
5.50 |
| • |
• |
SK1200 |
1200A |
15.50 |
8.25 |
Note: All 2UD,2UDF,2UDCP series enclosures that are 24.00" deep require a 48" or longer operating cable
| Frame Size |
Breaker Mechanism |
Flange Mounting Handle¹ |
Operating Cable² |
| E150 |
SCOM1A |
SCH1 |
SC3L |
| SE150/SF250 |
SCOM1EF |
SCH1 |
SC3L |
| SG600 |
SCOM1G |
SCH1 |
SC3L |
| SK1200 |
SCOM1K |
SCH2K |
SC3H |
1Add "X" for NEMA 4 or NEMA 4X Flange mounting handle.
2Operating Cables are available 3' to 10' lengths. In the table above, the number "3" in the part number indicates a 3' cable.
Space Occupied By Disconnect
1. GE Spectra-Flex™ Operating Cables permit circuit breaker locations separate from flange mounted handle mechanism.
2. See National Electrical Code 2005 article 430-10(b) for wiring space (Ref "P") needed for line side conductors.
3. Select shaft length based on location of circuit breaker in the enclosure. Maintain a 3" minimum bending radius for the Flex-Shaft™.
4. Space occupied by circuit breaker is calculated by:
Overall (Height "X" and Width "Y")
Minimum wire bend space (manufacturer specified)
Location "M" from right to left.
"K" = 7.88 when "A" = 60.13
"K" = 13.88 when "A" = 72.13
Charts reference Space Occupied by Disconnect Drawing. |
|
| |
|
Siemens I-T-E
I-T-E - Disconnect Switches (Max-Flex™ Operators) |
|
| Fits Enclosure Depth |
|
Amp |
|
|
Disconnect Height
"X" |
Disconnect Width
"Y" |
| 60.13 |
72.13 |
Switch |
Rating |
Fuse Clip |
Fuse Class |
| • |
• |
MCS603R |
30A |
No Fuse |
— |
5.52 |
6.13 |
| • |
• |
MCS603R |
30A |
30A-250V |
H,K,R |
8.11 |
6.13 |
| • |
• |
MCS603R |
30A |
30A-600V |
H,K,R |
10.11 |
6.13 |
| • |
• |
MCS603R |
30A |
30A-600V |
J |
8.48 |
6.13 |
| • |
• |
MCS606R |
60A |
No Fuse |
— |
5.52 |
6.13 |
| • |
• |
MCS606R |
60A |
60A-250V |
H,K,R |
7.86 |
6.13 |
| • |
• |
MCS606R |
60A |
60A-600V |
H,K,R |
10.38 |
6.13 |
| • |
• |
MCS606R |
60A |
60A-600V |
J |
8.36 |
6.13 |
| • |
• |
MCS610R |
100A |
No Fuse |
— |
7.59 |
7.38 |
| • |
• |
MCS610R |
100A |
100A-250V |
H,K,R |
11.85 |
7.38 |
| • |
• |
MCS610R |
100A |
100A-600V |
H,K,R |
13.85 |
7.38 |
| • |
• |
MCS610R |
100A |
100A-600V |
J |
10.60 |
7.38 |
| • |
• |
MCS620R |
200A |
No Fuse |
— |
9.00 |
9.17 |
| • |
• |
MCS620R |
200A |
200A-250V |
H,K,R |
14.70 |
9.17 |
| • |
• |
MCS620R |
200A |
200A-600V |
H,K,R |
17.20 |
9.17 |
| • |
• |
MCS620R |
200A |
200A-600V |
J |
13.32 |
9.17 |
Note: Enclosures that are 24.13" deep require a 48" Max-Flex™ cable (minimum cable length). |
|
| |
|
| Siemens I-T-E Max-Flex™ Operators (Circuit Breakers) |
|
Complete Operator
Mechansim |
Amp Rating |
Breaker
Frame Size |
|
Circuit Breaker
Height
"X" |
Circuit Breaker
Width
"Y" |
| Circuit Breaker Type |
| FHOE036 |
125A |
ED |
ED2, ED4, ED6, HED4, HED6 |
6.34 |
3.00 |
| FHOE036 |
125A |
CED |
CED6 |
9.58 |
3.00 |
| FHOF036 |
250A |
FD |
FXD6-A, FD6-A, HFD6, FXD6ETJ, HHFD6, HHFXD6
|
9.50 |
4.50 |
| FHOF036 |
250A |
CFD |
CFD6, CFD6-ETI |
14.25 |
4.50 |
| FHOJ036 |
400A, 600A |
JD, LD |
JXD2, LXD6, JD6, LD6, HJD6, HLD6, HHJD6, HHLD6,
HHJXD6, HHLDX6, JXD6-ETI, LXD6-ETI |
11.00 |
7.50 |
| FHOJ036 |
400A, 600A |
CJD,CLD |
CJD6, CLD6, CJD6-ETI, CLD6-ETI |
17.86 |
7.50 |
| FHOLMO36 |
800A |
LMD |
LMD6, LMXD6, HLMD6, HLMXD6, LMXD6-ETI |
16.00 |
9.00 |
| FHON048 |
800A, 1200A |
MD, ND |
MD6, ND6, MXD6, NXD6, HMD6, HND6, HMXD6,
HNXD6, CMD6, CND6, MXD6-ETI, CMD6-ETI |
24.00 |
9.00 |
|
| |