| Conditions |
Solution |
Advantages |
Disadvantages |
Maximum desired enclosure
temperature is 10°F or 5°C
above maximum outside ambient. |
Oversize the Enclosure |
Easy to implement, no maintenance. Maintains NEMA rating of the enclosure. |
Dissipates small amount of heat.
Larger enclosure size takes up more space. |
| Install ventilation louvers |
Economical solution, very little
maintenance, easy to implement. |
Dissipates limited amount of heat.
Dirt, oil or fluids could enter the
enclosure. NEMA rating is affected. |
| Install filter fans |
Less expensive than air/refrigeration systems. Relatively high amount of heat removed, some termperature control by using thermostats. |
Must maintain filters. NEMA rating can be affected. Limited use in hostile environments such as chemical applications. |
| Use an air/air heat exchanger |
Easy to install, small power consumption, temperature control via thermostat. Maintains NEMA rating of the enclosure. |
Must maintain filters. |
| Maximum desired enclosure temperature lower than maximum outside ambient. |
Use an air conditioner |
Easy to install. Temperature control via factory installed thermostat. Removes large amounts of heat. Maintains NEMA rating of enclosure, dehumidifies enclosure air. |
Must maintain filter. Generally not to be used when outside temperature is below 59°F (15°) or above 130°F (52°C). |