Guide de sélection d’armoires à deux portes

2UD, 2UDF et 2UDCP

ABB Controls
Disconnect switch:
  • Flange operated switch (fusible or non-fusible)
  • Shaft:
    • 12.13" deep enclosures use 
      DSFHS-12
    • 18.13" deep enclosures use 
      DSFHS-17
    • 24.13" deep enclosures, platform must be used with shaft (not included)
  • Handle: DSFHN-HS12
 
Circuit breaker:
  • Circuit breaker: ABB
  • Operating mechanism
  • Shaft:
    • 12.13" deep enclosures use 
      K7FHD-S12
    • 18.13" deep enclosures use 
      K7FHD-S17
    • 24.13" deep enclosures, platform must be used with shaft (not included)
  • Handle mechanism: K7FHD-HS12 
 
Allen Bradley
Bulletin 1494F flange mounted disconnect switch:
  • Disconnect switch
    Fuse block adaptor (if required)
  • Line and load connectors (if required)
 
1494D flange mounted circuit breaker operating mechanism, order:
  • Circuit breaker: C-H Westinghouse
  • Operating mechanism
  • Slide mechanism
 
Bulletin 1494U flange mounted disconnect switch, order:
  • Disconnect switch
  • Operating handle
  • Connecting rod (long)
  • Trailer fuse block kit (if required)
  • Fuse kit (if required)
  • Line and load connectors (if required)
 
Bulletin 1494U flange mounted circuit breaker operating mechanism, order:
  • Circuit breaker: C-H Westinghouse
  • Operating mechanism
  • Operating handle
  • Connecting rod (long)
  • When Allen Bradley 1494U devices are installed in 72" high enclosures with the operating handle mounted on the center post, an optional Allen Bradley channel support kit is recommended.
C-H Westinghouse
Type C361 disconnect switch:
  • Disconnect switch with an operating mechanism
  • Operating handle: C361H1 or C361H3
  • In 24.13" deep enclosures, platform must be used with shaft (not included)
 
Type C371 circuit breaker operating mechanism with a C-H Westinghouse circuit breaker:
  • Circuit breaker
  • Operating mechanism
  • Long operating rod (if required)
  • Operating handle:
    • 150 amp - C371H1 or C371H3
    • 250 through 600 amp - C371H5 or C371H7
 
Flex-Shaft™ handle mechanism:
  • Circuit breaker
  • Complete Flex-Shaft™ handle mechanism
 
General Electric
Disconnect switch:
  • Disconnect switch: Type QMR or QMW
  • Fuse clip kit or no-fuse kit
  • Flange handle: STDA1 or STDA2
  • Variable depth operating mechanism
  • Extended length drive rod (if required)
 
Circuit breaker:
  • Circuit breaker
  • Flange handle: STDA1 or STDA2
  • Variable depth operating mechanism
  • Extended length drive rod (if required)
  • An optional General Electric Flange Stiffener Kit (TDSR) is recommended when General Electric Type TDA devices are installed in 72.13" high enclosures with operating handle mounted on centerpost. Use with TDOM1, TDOM2, TDOM3, S100M1A, and S100M3 operating mechanisms. 
 
Circuit breaker with a Spectra-Flex™ cable operator:
  • Circuit breaker
  • Flange mounted handle mechanism:
    • 150 to 600 amps - STDA1
    • SK1200 - STDA3
  • Breaker mounted mechanism
  • Operating cable
I-T-E Siemens
Disconnect switch:
  • Basic switch (right-hand)
  • Fuse or no-fuse kit
  • Flange mounted handle: FHOHS
  • Switch operator
  • Operating cable:
    • FHOEC036 cable for 12.13" deep
    • FHOECO48 for 18.13" and 24.13" deep enclosures
 
Circuit breaker:
  • Circuit breaker
  • Pressure wire connectors
  • Flange mounted handle:
    • 100 to 600 - FHOH
    • 800 to 2000 - FHOHN
  • Circuit breaker operator mechanism
  • Operating cable:
    • 36" cable for 12.13" or 18.13" deep
    • 48" for 24.13" deep enclosures
  • These items are available from Siemens I-T-E as a complete mechanism with a 36" operating cable only Order items separately when using a 48" cable
 
Square D
Disconnect switch:
  • Disconnect switch with operating mechanism
  • Universal handle mechanism: Type A-1
  • Long operating rod (if required)
 
Circuit breaker:
  • Circuit breaker
  • Operating mechanism
  • Universal handle mechanism: Type A-1
  • Long operating rod (if required)
 
Class 9422 Type T disconnect switch with a cable mechanism:
  • Disconnect switch with operating mechanism: Class 9422, Type T
  • Handle mechanism: Class 9422, Type A-1
  • Cable mechanism: Class 9422 CFT_O, 3, 5, or 10 foot
 
Circuit breaker with a cable mechanism:
  • Circuit breaker: Square D
  • Handle mechanism: Class 9422, type A-1
  • Cable mechanism: Class 9422 CFT_O, 3, 5, or 10 foot
  • An optional Square D Channel flange Support Kit (9422-C1) is recommended when some Square D devices are installed in 72.13" high enclosures with operating handle mounted on centerpost.
ABB Controls

ABB Controls Disconnect Switches (Flange Mounted Operators)

Fits Enclosure Height ABB Switch 
Number
Amp       Space 
Occupied
  When 
A=60.13
P
When 
A=72.13
P
60.13 72.13 Rating Fuse Clip Fuse Class L M N
OETL-NF30-F 30A No Fuse 4.45 3.91 0.25 9.53 15.53
OETL-NF60-F 60A No Fuse 4.86 3.91 0.25 9.34 15.34
OETL-NF100-F 100A No Fuse 4.86 4.91 0.25 8.78 14.78
OETL-NF175-F 175A No Fuse 7.30 6.62 0.25 6.53 12.53
OETL-NF200-F 200A No Fuse 7.36 7.41 0.25 6.53 12.53
OESA-F30J6-F 30A 30A-600V J 4.28 6.70 0.25 7.85 13.86
OESA-F60J6-F 60A 60A-600V J 4.28 6.39 0.25 7.85 13.86
OESA-F100J6-F 100A 100A-600V 6.54 7.78 0.25 7.42 13.42
      200A²              
¹ J type fuse clips are standard. If 600 V Type “T” fuse clips are desired order T type fuse adaptor kit.
² 200 A available by using non-fusible 200A switch and a trailing fuse block. (consult ABB)   ABB Controls Circuit Breaker (Flange Mounted Operators)
Fits Enclosure Height ISOMAX Circuit
Breaker
Amp 
Rating
Operating 
Mechanism
Frame 
Type
Space Occupied   When 
A=60.13
P
When 
A=72.13
P
60.13 72.13 L M N
S1N100TL 100A K2FHD-M S1 5.30 4.60 0.63 8.33 14.33
S3N150TW 150A K3FHD-M S3 6.67 5.02 0.63 7.73 13.73
S3N225TW 225A K3FHD-M S3 6.67 5.02 0.63 7.73 13.73
S4N250BW 250A K4FHD-M S4 8.45 5.02 0.63 6.20 12.20
S5N400TW 400A K5FHD-M S5 8.45 6.40 0.63 6.20 12.20
S6N600TW 600A K6FHD-M S6 8.33 10.00 0.63 5.53 11.53
S6N800TW 800A K6FHD-M S6 8.33 10.00 0.63 5.53 11.53
"K" = 7.88 when "A" = 60.13
"K" = 13.88 when "A" = 72.13 Charts reference Space Occupied by Disconnect Drawing.  

Allen Bradley

Allen Bradley 1494F Disconnect Switches
Fits Enclosure Height Allen Bradley Switch 
Number
Amp 
Rating
      Space 
Occupied
  When 
A=60.13
P
When 
A=72.13
P
60.13 72.13 Fuse Clip Fuse Class L N
N30 30A No Fuse 4.62 6.50 0.63 5.31 11.31
NF30 30A 30A-250V H, K, R 6.50 6.50 0.63 5.31 11.31
NF30 30A 60A-250V H, K, R 7.25 6.50 0.63 5.31 11.31
NF30 30A 30A-600V H, K, R 9.25 6.50 0.63 5.31 11.31
NF30 30A 60A-600V H, K, R 9.75 6.50 0.63 5.31 11.31
NF30 30A 30A-600V J 6.50 6.50 0.63 5.31 11.31
NF30 30A 60A-600V J 6.62 6.50 0.63 5.31 11.31
N60 60A No Fuse 4.62 6.50 0.63 4.62 10.62
NF60 60A 30A-600V H, K, R 10.38 6.50 0.63 4.62 10.62
NF60 60A 60A-250V H, K, R 8.38 6.50 0.63 4.62 10.62
NF60 60A 100A-250V H, K, R 10.88 6.50 0.63 4.62 10.62
NF60 60A 60A-600V H, K, R 10.88 6.50 0.63 4.62 10.62
NF60 60A 100A-600V H, K, R 12.88 6.62 0.63 4.62 10.62
NF60 60A 60A-600V J 7.75 6.50 0.63 4.62 10.62
NF60 60A 100A-600V J 9.75 6.50 0.63 4.62 10.62
  N100 100A No Fuse 4.62 7.25 0.63 8.75
  NF100 100A 100A-250V H, K, R 11.38 7.38 0.63 8.75
  NF100 100A 200A-250V H, K, R 12.25 7.62 0.63 8.75
  NF100 100A 100A-600V H, K, R 13.38 7.50 0.63 8.75
  NF100 100A 200A-600V H, K, R 14.75 7.75 0.63 8.75
  NF100 100A 100A-600V J 10.12 7.38 0.63 8.75
  NF100 100A 200A-600V J 10.88 7.50 0.63 8.75
  N200 200A No Fuse 7.12 10.38 0.56 7.13
  NF200 200A 200A-250V H, K, R 15.00 10.38 0.56 7.13
  NF200 200A 400A-250V H, K, R 16.56 10.75 0.56 7.13
  NF200 200A 200A-600V H, K, R 17.56 10.38 0.56 7.13
  NF200 200A 400A-600V H, K, R 19.56 11.00 0.56 7.13
  NF200 200A 200A-600V J 13.69 10.38 0.56 7.13
  NF200 200A 400A-600V J 15.00 10.62 0.56 7.13

¹"M" dimension does not allow for auxiliary switches. Refer to Allen Bradley instructions if additional space is required.  

Allen Bradley 1494D Operators (Circuit Breakers)

Fits Enclosure Height Alan Bradley 
Type Number
Amp 
Rating
Circuit Breker Type   Space
Occupied
  When 
A=60.13
P
When 
A=72.13
P
60.13 72.13 L N
N4/N40 150A C-H Westinghouse 
EHD,FD,FDB,FDC,HFD,HMCP
5.81 4.56 0.63 5.25 11.25
N5/N55 225A General Electric 
TFK, THFK, TFC
8.81 4.75 0.63 4.44 10.44
N5/N50 250A C-H Westinghouse
JD,JDB,JDC,HJD,HMCP
8.81 4.75 0.63 4.44 10.44
  N5/N60 400A C-H Westinghouse 
KD,KDB,DK,HKD,HMCP
8.81 5.88 0.63 10.50

1 "M" dimension does not allow for auxiliary switches. Refer to Allen Bradley instructions if additional space is required.
"K" = 5.88 when "A" = 60.13
"K" = 11.88 when "A" = 72.13 (except 200A switches)
"K" = 10.56 when "A" = 72.13 (200A switches only).
 

Allen Bradley 1494U Operators (Disconnect Switches)

Fits Enclosure Height Alan Bradley Switch
Number
Amp       Space 
Occupied
  When 
A=60.13
P
When 
A=72.13
P
60.13 72.13 Rating Fuse Clip Fuse Class L N
DS30 30A No Fuse 3.88 6.75 1.06 6.00 12.00
DS30 30A 30A-250V H,K,R 5.25 6.75 1.06 6.00 12.00
DS30 30A 30A-600V H,K,R 8.00 6.75 1.06 6.00 12.00
DS30 30A 30A-600V J 5.25 6.75 1.06 6.00 12.00
DS30 30A 60A-250V H,K 6.00 6.75 1.06 6.00 12.00
DS30 30A 60A-600V H,K 8.50 6.75 1.06 6.00 12.00
DS30 30A 60A-600V J 5.38 6.75 1.06 6.00 12.00
DS60 60A No Fuse 3.88 6.75 1.06 5.81 11.81
DS60 60A 60A-250V H,K,R 6.00 6.75 1.06 5.81 11.81
DS60 60A 60A-600V H,K,R 8.50 6.75 1.06 5.81 11.81
DS60 60A 60A-600V J 5.38 6.75 1.06 5.81 11.81
DS60 60A 30A-600V H,K,R 8.00 6.75 1.06 5.81 11.81
DS60 60A 100A-250V H,K 8.50 6.75 1.06 5.81 11.81
DS60 60A 100A-600V H,K 10.50 6.75 1.06 5.81 11.81
DS60 60A 100A-600V J 7.25 6.75 1.06 5.81 11.81
DS100¹ 100A No Fuse 3.88 6.75 1.06 5.81 11.81
DS100¹ 100A 100A-250V H,K,R 8.12 6.75 1.06 5.81 11.81
DS100¹ 100A 100A-600V H,K,R 10.12 6.75 1.06 5.81 11.81
DS100¹ 100A 100A-600V J 6.80 6.75 1.06 5.81 11.81
DS100¹ 100A 60A-600V H,K,R 10.12 6.75 1.06 5.81 11.81
DS100¹ 100A 60A-600V J 8.88 6.75 1.06 5.81 11.81
  DS2001 200A No Fuse 4.75 8.00 1.06 10.34
  DS2001 200A 200A-250V H,K,R 10.88 8.00 1.06 10.34
  DS2001 200A 200A-600V H,K,R 13.88 8.00 1.06 10.34
  DS2001 200A 200A-600V J 9.50 8.00 1.06 10.34
  DS2001 200A 100A-600V H,K,R 12.00 8.00 1.06 10.34
  DS2001 200A 100A-600V J 8.75 8.00 1.06 10.34

1 Series B
2 "M" dimension does not allow for auxiliary switches
 

Allen Bradley 1494U Operators (Circuit Breakers)

Fits Enclosure Height Alan Bradley
Type Number
Amp     Space 
Occupied
  When 
A=60.13
P
When
A=72.13
P
60.13 72.13 Rating Circuit Breker Type L M1 N
M40 15A-150A C-H Westinghouse 
EHD,FD,FDB,FDC,HFD,HMCP
5.00 4.62 1.06 7.25 13.25
M50 70A-250A C-H Westinghouse 
JD,JDB,JDC,HJD,HMCP
9.75 4.88 1.06 6.81 12.81
  M60 100A-400A C-H Westinghouse 
KD,KDB,DK,HKD,HMCP
9.69 6.25 1.06 12.62

1 "M" dimension does not allow for auxiliary switches. Refer to Allen Bradley instructions if additional space is required.
"K" = 7.88 when "A" = 60.13
"K" = 13.88 when "A" = 72.13  

Cutler Hammer

Cutler Hammer C361 Disconnect Switches

Fits Enclosure Height Cutler Hammer
Type Number
Amp       Space 
Occupied
  When 
A=60.13
P
When 
A=72.13
P
60.13 72.13 Rating Fuse Clip Fuse Class L M N
C361NC 30A No Fuse 5.75 7.55 0.63 6.50 12.50
C361SC21 30A 30A-250V H, K, R 8.38 7.55 0.63 6.50 12.50
C361SC61 30A 60A-250V H, K, R 8.38 7.55 0.63 6.50 12.50
C361SC61 30A 30A-600V H, J, K, R 8.38 7.55 0.63 6.50 12.50
C361ND 60A No Fuse 5.75 7.55 0.63 6.50 12.50
C361SD22 60A 60A-250V H, K, R 8.38 7.55 0.63 6.50 12.50
C361SD22 60A 30A-600V J 8.38 7.55 0.63 6.50 12.50
C361SD62 60A 60A-600V H, K, R 8.38 7.55 0.63 6.50 12.50
C361SD62 60A 60A-600V J 8.38 7.55 0.63 6.50 12.50
C361NE 100A No Fuse 5.56 9.07 0.63 6.06 12.06
C361SE263 100A 100A-250V H, K, R 10.31 9.07 0.63 6.06 12.06
C361SE263 100A 100A-600V H, K, R 10.31 9.07 0.63 6.06 12.06
C361SE263 100A 100A-600V J 10.31 9.07 0.63 6.06 12.06
C361NF 200A No Fuse 13.06 10.12 0.63 4.06 10.12
C361SF264 200A 200A-250V H, K, R 13.06 10.12 0.63 4.06 10.12
C361SF264 200A 200A-600V H, K, R, J 13.06 10.12 0.63 4.06 10.12
  Cutler Hammer C371 Circuit Breaker (C-H Westinghouse Circuit Breakers)
Fits Enclosure Height Cutler Hammer 
Mechanisms
Amp     Space Occupied   When 
A=60.13
P
When 
A=72.13
P
60.13 72.13 Rating Frame Type L M N
C371E 150A F Frame EHD,FDB,FD,HFD,FDC 6.00 5.62 0.63 7.62 13.62
C371E 150A F Frame HMCP 6.00 5.62 0.63 7.62 13.62
¹ C371F 250A J Frame JDB,JD,HJD,JDC 8.94 8.12 0.63 7.50 13.50
¹ C371F 250A J Frame HMCP 10.94 8.12 0.63 7.50 13.50
¹ C371F 400A K Frame DK,KDB,KD,HKD 9.75 8.12 0.63 7.00 13.00
¹ C371F 400A K Frame HMCP 9.75 8.12 0.63 7.00 13.00
  ² C371G 600A L Frame LD,HLD,LDC 8.44 12.00 0.63 - 11.38
  ² C371G 600A L Frame HMCP 8.44 12.00 0.63 - 11.38
1Wire bend space "P" does not allow cable size larger than 4/0 AWG in a 60.13" tall enclosures.
2Wire bend space "P" does not allow cable size larger than 300 MCM.
"K" = 7.88 when "A" = 60.13
"K" = 13.88 when "A" = 72.13
Charts reference Space Occupied by Disconnect Drawing.   Cutler Hammer Flex-Shaft™ Operator Mechanisms (C-H Westinghouse Circuit Breakers)
Complete Operator     Breaker Height "X" Breaker Width "Y"
Mechanisms Amp  Rating Frame Type (in inches) (in inches)
F1S03 150A F Frame EHD,FDB,FD,HFD 6.00 4.12
F1S03 150A  F Frame HCMP 6.00 4.12
F2S03 250A J  Frame JDB,JD,HJD,JDC 10.00 4.12
F2S03 250A J  Frame HCMP 10.00 4.12
F3S03 400A K  Frame DK,KDB,KD,HKD 10.12 5.50
F3S03 400A K  Frame HCMP 12.45 5.50
F4S04 600A L  Frame LD,HLD,LDC 10.75 8.25
F7S04 800A M Frame MD,MDS 16.00 8.25
F5S04 1200A N Frame ND,HND,NDC 16.00 8.25
F6S04 2500A R Frame RD,CRD, RDC 16.00 15.50
  • Overall (Height "X" and Width "Y")
  • Minimum wire bend space (manufacturer specified)
  • Location "M" from right to left.

Charts reference Space Occupied by Disconnect Drawing

      General Electric 

General Electric Type STDA Disconnect Switche Operators  
Fits Enclosure Height General Electric 
Switch
Mechanisms
Amp 
Rating
      Space 
Occupied
M
  When 
A=60.13
P
When 
A=72.13
P
60.13 72.13 Fuse Clip Fuse Class L N
TDOM1A 30A No Fuse - 6.88 5.38 0.63 8.38 14.38
TDOM1A 30A 30A-250V H, R 6.88 5.38 0.63 8.38 14.38
TDOM1B 30A 30A-600V H, R 11.5 5.38 0.63 8.38 14.38
TDOM1B 30A 60A-250V H, R 11.5 5.38 0.63 8.38 14.38
TDOM1B 30A 60A-600V H, R 11.5 5.38 0.63 8.38 14.38
TDOM1A 60A No Fuse - 6.88 5.38 0.63 8.38 14.38
TDOM1B 60A 60A-250V H, R 11.5 5.38 0.63 8.38 14.38
TDOM1B 60A 60A-600V H, R 11.5 5.38 0.63 8.38 14.38
TDOM1B 60A 100A-250V H, R 11.5 5.38 0.63 8.38 14.38
TDOM1B 60A 100A-600V H, R 11.5 5.38 0.63 8.38 14.38
TDOM1A 100A No Fuse - 6.88 5.38 0.63 8.38 14.38
TDOM1B 100A 100A-250V H, R 11.5 5.38 0.63 8.38 14.38
TDOM1B 100A 100A-600V H, R 11.5 5.38 0.63 8.38 14.38
TDOM1B 100A 200A-250V H, R 11.5 5.38 0.63 8.38 14.38
TDOM1B 100A 200A-600V H, R 11.5 5.38 0.63 8.38 14.38
TDOM2 200A No Fuse - 7 9.25 0.63 5.69 11.69
TDOM2 200A 200A-250V H, R 15.38 9.25 0.63 5.69 11.69
TDOM2 200A 200A-600V H, R 15.38 9.25 0.63 5.69 11.69
      General Electric Type STDA Circuit Breaker Operators  
Fits Enclosure Height General Electric 
Circuit Breaker
Mechanisms
Amp 
Rating
Frame Type   Space Occupied When 
A=60.13
P
When 
A=72.13
P
60.13 72.13 L M N
TDOM1A 150A TEB, TED, THED 6.88 5.38 0.63 7.24 13.24
TDOM1A 150A TEC 6.88 5.38 0.63 7.24 13.24
TDOM1B 150A TB1 11.50 5.38 0.63 7.24 13.24
TDOM1B 150A TEC, TECL 11.50 5.38 0.63 7.24 13.24
TDOM1C 150A TEL 6.88 5.38 0.63 7.24 13.24
TDOM1D 150A THLC1 6.88 5.38 0.63 5.87 11.87
TDOM3 225A TFJ 10.38 5.88 0.63 6.81 12.81
TDOM3 225A TFK, THFK, TFL 10.38 5.88 0.63 6.81 12.81
  TDOM4 400A TJJ, TJK4, THJK4, TJL4V 8.25 9.50 0.63 11.91
  TDOM4 600A TJK6, THJK6, TJ4V, TJL4V 8.25 9.50 0.63 11.91
  TDOM5 400A TB4, TJH6S 14.25 9.50 0.63 11.91
  TDOM6 225A TLB2, THLC2 11.75 9.50 0.63 11.35
  TDOM6 400A TLB4, THLC4 11.75 9.50 0.63 9.97
SDOM1A 150A SE150 6.88 5.38 0.63 7.24 13.24
SDOM3 250A SPECTRA SF250 10.38 5.88 0.63 6.81 11.88
  SDOM4 600A SPECTRA SG600 10.00 7.12 0.63 9.18

"K" = 7.88 when "A" = 60.13
"K" = 13.88 when "A" = 72.13       General Electric Circuit Breakers (Spectra-Flex™ Cable Operators)  
Fits Enclosure Height     Circuit Breaker Height Circuit Breaker Width
60.13 72.13 Frame Size Max Amp Rating "X" "Y"
E150 150A 6.31 4.12
SE150 150A 6.31 4.12
SF250 250A 10.12 4.12
SG600 600A 10.09 5.50
SK1200 1200A 15.50 8.25

Note: All 2UD,2UDF,2UDCP series enclosures that are 24.00" deep require a 48" or longer operating cable
 
Frame Size Breaker Mechanism Flange Mounting Handle¹ Operating Cable²
E150 SCOM1A SCH1 SC3L
SE150/SF250 SCOM1EF SCH1 SC3L
SG600 SCOM1G SCH1 SC3L
SK1200 SCOM1K SCH2K SC3H
1Add "X" for NEMA 4 or NEMA 4X Flange mounting handle.
2Operating Cables are available 3' to 10' lengths. In the table above, the number "3" in the part number indicates a 3' cable.

Space Occupied By Disconnect
1. GE Spectra-Flex™ Operating Cables permit circuit breaker locations separate from flange mounted handle mechanism.
2. See National Electrical Code 2005 article 430-10(b) for wiring space (Ref "P") needed for line side conductors.
3. Select shaft length based on location of circuit breaker in the enclosure. Maintain a 3" minimum bending radius for the Flex-Shaft™.
4. Space occupied by circuit breaker is calculated by:
Overall (Height "X" and Width "Y")
Minimum wire bend space (manufacturer specified)
Location "M" from right to left.

"K" = 7.88 when "A" = 60.13
"K" = 13.88 when "A" = 72.13

Charts reference Space Occupied by Disconnect Drawing.

Siemens I-T-E 

I-T-E - Disconnect Switches (Max-Flex™ Operators)  
Fits Enclosure Depth   Amp     Disconnect Height 
"X"
Disconnect Width 
"Y"
60.13 72.13  Switch Rating Fuse Clip Fuse Class
MCS603R 30A No Fuse 5.52 6.13
MCS603R 30A 30A-250V H,K,R 8.11 6.13
MCS603R 30A 30A-600V H,K,R 10.11 6.13
MCS603R 30A 30A-600V J 8.48 6.13
MCS606R 60A No Fuse 5.52 6.13
MCS606R 60A 60A-250V H,K,R 7.86 6.13
MCS606R 60A 60A-600V H,K,R 10.38 6.13
MCS606R 60A 60A-600V J 8.36 6.13
MCS610R 100A No Fuse 7.59 7.38
MCS610R 100A 100A-250V H,K,R 11.85 7.38
MCS610R 100A 100A-600V H,K,R 13.85 7.38
MCS610R 100A 100A-600V J 10.60 7.38
MCS620R 200A No Fuse 9.00 9.17
MCS620R 200A 200A-250V H,K,R 14.70 9.17
MCS620R 200A 200A-600V H,K,R 17.20 9.17
MCS620R 200A 200A-600V J 13.32 9.17

Note: Enclosures that are 24.13" deep require a 48" Max-Flex™ cable (minimum cable length).       Siemens I-T-E Max-Flex™ Operators (Circuit Breakers)  
Complete Operator 
Mechansim
Amp Rating Breaker 
Frame Size
  Circuit Breaker
Height
"X"
Circuit Breaker
Width
"Y"
Circuit Breaker Type
FHOE036 125A ED ED2, ED4, ED6, HED4, HED6 6.34 3.00
FHOE036 125A CED CED6 9.58 3.00
FHOF036 250A FD FXD6-A, FD6-A, HFD6, FXD6ETJ, HHFD6, HHFXD6 9.50 4.50
FHOF036 250A CFD CFD6, CFD6-ETI 14.25 4.50
FHOJ036 400A, 600A JD, LD JXD2, LXD6, JD6, LD6, HJD6, HLD6, HHJD6, HHLD6, 
HHJXD6, HHLDX6, JXD6-ETI, LXD6-ETI
11.00 7.50
FHOJ036 400A, 600A CJD,CLD CJD6, CLD6, CJD6-ETI, CLD6-ETI 17.86 7.50
FHOLMO36 800A LMD LMD6, LMXD6, HLMD6, HLMXD6, LMXD6-ETI 16.00 9.00
FHON048 800A, 1200A MD, ND MD6, ND6, MXD6, NXD6, HMD6, HND6, HMXD6,
HNXD6, CMD6, CND6, MXD6-ETI, CMD6-ETI
24.00 9.00
FHONO48 1600A, 2000A PD,RD PD6, RD6, PXD6, RXD6, HPD6, HRD6, HPXD6, 
HRXD6, CPD6
24.50(2) 13.63(2)
  • Overall (Height "X" and Width "Y")
  • Minimum wire bend space (manufacturer specified)
  • Location "M" from right to left.

Charts reference Space Occupied by Disconnect Drawing.

Square D

Square D Class 9422 Variable Depth Disconnect Switches  
Fits Enclosure Height Square D 
Amp Number
Amp
Rating
    Space Occupied   When 
A=60.13
P
When 
A=72.13
P
60.13 72.13 Fuse Clip Fuse Class L M N
TCN-30 30A No Fuse 3.80 6.97 0.63 6.75 12.75
TCF-30 30A 30A-250V H, K, R 5.53 6.97 0.63 6.75 12.75
TCF-33 30A 30A-600V H, K, R 8.15 6.97 0.63 6.75 12.75
TCF-33 30A 60A-250V H, K, R 6.15 6.97 0.63 6.75 12.75
TCF-33 30A 30A-600V J 5.53 6.97 0.63 6.75 12.75
TDN-60 60A No Fuse 3.80 6.97 0.63 6.75 12.75
TDF-60 60A 30A-600V H, K, R 8.15 6.97 0.63 6.75 12.75
TDF-60 60A 60A-250V H, K, R 6.15 6.97 0.63 6.75 12.75
TDF-63 60A 60A-600V H, K, R 8.65 6.97 0.63 6.75 12.75
TDF-63 60A 60A-600V J 5.53 6.97 0.63 6.75 12.75
TEN-10 100A No Fuse 3.80 6.97 0.63 6.62 12.62
TEF-10 100A 100A-250V H, K, R 8.25 6.97 0.63 6.62 12.62
TEF-10 100A 100A-600V H, K, R 10.25 6.97 0.63 6.62 12.62
TEF-10 100A 100A-600V J 7.05 6.97 0.63 6.62 12.62
TEF-13 100A 200A-600V J 0.63 6.62 12.62
TC-1 30A No Fuse 5.75 6.12 0.63 5.88 11.88
TC-2 30A 30A-250V H, K, R 5.75 6.12 0.63 5.88 11.88
TC-3 30A 30A-600V H, K, R 7.75 6.12 0.63 5.88 11.88
TC-3 30A 60A-250V H, K, R 5.88 6.12 0.63 5.88 11.88
TC-3 30A 30A-600V J 5.75 6.12 0.63 5.88 11.88
TD-1 60A No Fuse 6.38 6.75 0.63 6.75 12.75
TD-2 60A 30A-600V H, K, R 8.50 6.75 0.63 6.75 12.75
TD-2 60A 60A-250V H, K, R 6.50 6.75 0.63 6.75 12.75
TD-3 60A 60A-600V H, K, R 9.00 6.75 0.63 6.75 12.75
TD-3 60A 60A-600V J 6.38 6.75 0.63 6.75 12.75
TE-1 100A No Fuse 4.75 8.50 0.63 6.50 12.50
TE-2 100A 100A-250V H, K, R 7.50 8.50 0.63 6.50 12.50
TE-2 100A 100A-600V H, K, R 9.50 8.50 0.63 6.50 12.50
TE-2 100A 100A-600V J 6.25 8.50 0.63 6.50 12.50
TE-3 100A 200A-600V J 13.75 8.50 0.63 6.50 12.50
TF-1 200A No Fuse 5.50 11.75 0.63 5.12 11.12
TF-2 200A 200A-250V H, K, R 11.50 11.75 0.63 5.12 11.12
TF-2 200A 200A-600V H, K, R 14.00 11.75 0.63 5.12 11.12
TF-2 200A 200A-600V J 10.12 11.75 0.63 5.12 11.12
TF-3 200A 400A-600V J 14.50 11.75 0.63 5.12 11.12
      Square D Class 9422 Variable Depth Operators (Circuit Breakers)  
Fits Enclosure Depth Square D Type 
Number
Amp 
Rating
  Space Occupied   When 
A=60.13
P
When 
A=72.13
P
60.13 72.13 Frame Size L M N
RG-1 75A GJL 3.53 3.87 0.63 6.69 12.69
RG-1 100A GJL 3.53 3.87 0.63 6.69 12.69
RN-1 100A FAL, FHL 5.12 5.38 0.63 6.88 12.88
RP-1 250A KAL, KHL 7.12 5.75 0.63 7.56 13.56
  RR-1 400A LAL, LHL, Q4L 7.62 8.88 0.63 9.25
      Square D Class 9422 Disconnect Switches (Cable Mechanism 9422-CFT30 and 9422A-1 Handle Mechanism)  
Fits Enclosure Depth Square D 
Type Number
Amp 
Rating
Fuse Clip Fuse Class Disconnect Height 
"X"
Disconnect Width 
"Y"
A=60.13 A=72.13
P P
TCN-30 30A No Fuse 5.90 6.20
TCF-30 30A 30A-250V H, K, R 7.50 6.20
TCF-33 30A 30A-600V H, K, R 10.15 6.20
TCF-33 30A 60A-250V H, K, R 8.15 6.20
TCF-33 30A 30A-600V J 7.50 6.20
TDN-60 60A No Fuse 5.90 6.20
TDF-60 60A 30A-600V H, K, R 10.15 6.20
TDF-60 60A 60A-250V H, K, R 8.15 6.20
TDF-63 60A 60A-600V H, K, R 10.65 6.20
TDF-63 60A 60A-600V J 7.50 6.20
TEN-10 100A No Fuse 5.90 6.20
TEF-10 100A 100A-250V H, K, R 10.35 6.20
TEF-10 100A 100A-600V H, K, R 10.35 6.20
TEF-10 100A 100A-600V J 10.35 6.20
      Square D Class 9422 Cable Mechanism (Circuit Breakers)  
Fits Enclosure Depth          
A=60.13 A=72.13       Circuit Breaker Circuit Breaker
P P Cable Type Switch Amp Rating Frame Type Height "X" Width "Y"
9422 CGJ30 75A GJL 4.75 3.50
9422 CEJ30 100A GJL 4.75 3.50
9422 CFA30 100A FAL,FHL 6.00 4.50
9422 CKA30 250A KAL,KHL 8.00 4.50
9422 CLA30 400A LAL,LHL,Q4L 11.00 6.00

Use cable mechanism with circuit breaker and 9422-A1 handle mechanism
Cable operators are offered in 3’, 5’, and 10’ lengths. Last 2 digits of part numbers above (30) are for 3’ cables

Space Occupied By Disconnect Switch
1. Square D Cable System permits circuit breaker locations separate from flange mounted handle mechanism.
2. See National Electrical Code 2005 article 430-10(b) for wiring space (Ref “P”) needed for line side conductors.
3. Select cable mechanism length based on disconnect location in enclosure. See Square D instructions for minimum cable bend radius.
4. Space occupied by circuit breaker is calculated by:

 
  • Overall (Height "X" and Width "Y")
  • Minimum wire bend space (manufacturer specified)

"K" = 7.88 when "A" = 60.13
"K" = 13.88 when "A" = 72.13

Charts reference Space Occupied by Disconnect Drawing.