Product Resources
Downloads
Share this Product
Description
- Designed to use various water sources to cool enclosures where ambient conditions involve high temperatures, harsh conditions or are subject to frequent wash-down.
Standards
- UL, cUL, and CE
- Complies with
- NEMA 3R, 4, 4X
Features
- Compatible with chilled water/glycol, tower water and other circulated coolants
- Integrated thermostat & solenoid value with alarm contact provides automatic temperature control
- Rugged (10 bar) copper tube / aluminum fin heat exchanger with 1/2" barb connection
- Side, door or internal mounting provides complete installation flexibility
- Low noise, maintenance-free design
- Exterior case, galvanized steel construction finish RAL7035 Light Gray or 304 SS
Accessories
Part Details
Click Part No, below, for details (e.g., Product drawings, assembly instructions, ship weight)
Units shown: inch. Switch units to: mm
Part Number | H | W | D |
---|---|---|---|
PWS3062A115N4LG | 24.10 | 10.13 | 5.62 |
PWS3062A230N4LG | 24.10 | 10.13 | 5.62 |
PWS3062A115N4SS | 24.10 | 10.13 | 5.62 |
PWS3062A230N4SS | 24.10 | 10.13 | 5.62 |
PWS3082A115N4LG | 24.10 | 10.13 | 5.62 |
PWS3082A230N4LG | 24.10 | 10.13 | 5.62 |
PWS3082A115N4SS | 24.10 | 10.13 | 5.62 |
PWS3082A230N4SS | 24.10 | 10.13 | 5.62 |
Electrical Data | PWS3062 | PWS3082 | ||
---|---|---|---|---|
Rated Voltage | 115 | 230 | 115 | 230 |
Frequency Hz | 60 | 50/60 | 60 | 50/60 |
Power Consumption | 28.2 W | 30.4 W | 21.3 W | 18.4 W |
Running Amps | 0.33 | 0.15 | 0.235 | 0.126 |
Connection | Terminal Block | Terminal Block |
Cooling Data | PWS3062 | PWS3082 |
---|---|---|
Cooling Capacity Enclosure +95F (+35C) Water +50F (+10C) | 2216 BTU/h (650 W) | 2898 BTU/h (850 W) |
Adjustable Control Range (Factory setting +95F ( +35C) | +50 to +104 F +10 to +50 C | +50 to +104 F +10 to +50 C |
Flow Rate at Rated Capacity | 2 GPM 450 L/h | 2GPM 450L/h |
Operting Pressure | 14.5 - 145 PSI 1 - 10 bar | 14.5 - 145 PSI 1 - 10 bar |
Ambient Air Temp | + 36/140 F +2/+55 C | + 36/140 F +2/+55 C |
Air Volume | 100 CFM 170 CM/h | 125 CFM 213 CM/h |
Data subject to change without notice.
Tags: climate, temperature, air/water, heat exchanger, Type 4X, Type 3R, high temperature