Description
- Designed to use various water sources to cool enclosures where ambient conditions involve high temperatures, harsh conditions or are subject to frequent wash-down.
Standards
- UL, cUL, and CE
- Complies with
- NEMA 3R, 4, 4X
Features
- Compatible with chilled water/glycol, tower water and other circulated coolants
- Integrated thermostat & solenoid value with alarm contact provides automatic temperature control
- Rugged (10 bar) copper tube / aluminum fin heat exchanger with 1/2" barb connection
- Side, door or internal mounting provides complete installation flexibility
- Low noise, maintenance-free design
- Exterior case, galvanized steel construction finish RAL7035 Light Gray or 304 SS
Accessories
Part Details
Click Part No, below, for details (e.g., Product drawings, assembly instructions, ship weight)
Units shown: inch. Switch units to: mm
Part Number | H | W | D |
---|---|---|---|
PWS3202A115N4LG | 51.89 | 15.76 | 9.07 |
PWS3202A230N4LG | 51.89 | 15.76 | 9.07 |
PWS3202A115N4SS | 51.89 | 15.76 | 9.07 |
PWS3202A230N4SS | 51.89 | 15.76 | 9.07 |
PWS3302A115N4LG | 51.89 | 15.76 | 9.07 |
PWS3302A230N4LG | 51.89 | 15.76 | 9.07 |
PWS3302A115N4SS | 51.89 | 15.76 | 9.07 |
PWS3302A230N4SS | 51.89 | 15.76 | 9.07 |
Electrical Data | PWS3202 | PWS3302 | ||
---|---|---|---|---|
Rated Voltage | 115 | 230 | 115 | 230 |
Frequency Hz | 60 | 50/60 | 60 | 50/60 |
Power Consumption | 77.6 W | 66.2 W | 77.9 W | 59.0 W |
Running Amps | 0.69 | 0.31 | 0.69 | 0.31 |
Connection | Terminal Block | Terminal Block |
Cooling Data | PWS3202 | PWS3302 |
---|---|---|
Cooling Capacity Enclosure +95F (+35C) Water +50F (+10C) | 7165 BTU/h (2100 W) | 12283 BTU/h (3600 W) |
Adjustable Control Range (Factory setting +95F ( +35C) | +45 to +113 F +10 to +50 C | +46 to +122 F +8 to +50 C |
Flow Rate at Rated Capacity | 2 GPM 450 L/h | 2GPM 450L/h |
Operting Pressure | 14.5 - 145 PSI 1 - 10 bar | 14.5 - 145 PSI 1 - 10 bar |
Ambient Air Temp | + 36/140 F +2/+60 C | + 36/158 F +2/+65 C |
Air Volume | 300 CFM 510 CM/h | 315 CFM 535 CM/h |
Data subject to change without notice.
Tags: climate, temperature, air/water, heat exchanger, Type 4X, Type 3R, high temperature