Product Resources
Links
Share this Product
Description
- Designed to provide recirculated coolant for most industrial applications air/water heat exchangers, process cooling, machine hydraulics or motor cooling.
Standards
- CCE Series – UL 508-A, CE
- EB80-160 WT Series – UL 508-A, CE
Features
- Pre-engineered packaged design includes refrigeration, cooling tank/pump and operating controls for plug and play operation
- CCE Series compact design for cooling capacities up to 22,000 BTU/H
- EB 2.0 Series for cooling capacities 27,000 to 151,000 BTU/H - Larger sizes and High Temperature units also available
- EB80-160WT standard features include: Programmable smart controller, Hot gas by-pass refrigerant circuit, internal hydraulic by-pass circuit, electrical tank level switch and more.
- Both series are suitable for indoor installations
- Ambient operating temperature range 45°F to 113°F, 15°C to 45°C
- Several product options can be added - vary by unit, please ask for details
- Exterior case, galvanized steel frame coated with RAL7035 powder coated finish
Part Details
Click Part No, below, for details (e.g., Product drawings, assembly instructions, ship weight)
Part numbers with stars are new sizes or packaging configurations.
Units shown: inch. Switch units to: mm
Model | Cooling Capacity | Voltage AC | Pump Flow Rate | Tank Capacity Gallons | Coolant Connections | Overall Dimensions | ||
---|---|---|---|---|---|---|---|---|
Number | Ambient +90F(+32C) Water +64F(+18C) | 60 Hz | GPM (l/h) | (Litres) | (NPT-F) | Height | Width | Depth |
CCE6301 | 8189 BTU/H (2400 Watts) | 230 | 2.3 (520 l/h) | 3.0 (11L) | 1/2" | 22.50 | 19.40 | 23.62 |
CCE6401 | 12000 BTU/H (3500 Watts) | 460 3 Phase | 6.0 (1360 l/h) | 7.0 (26L) | 3/4" | 36.27 | 26.61 | 23.62 |
CCE6601 | 22000 BTU/H (6500 Watts) | 460 3 Phase | 6.0 (1360 l/h) | 7.0 (26L) | 3/4" | 36.27 | 26.61 | 23.62 |
EB80WT | 27000 BTU/H (8000 Watts) | 460 3 Phase | 6.0 (1360 l/h) | 13.0 (50L) | 3/4" | 54.17 | 23.62 | 29.94 |
EB95WT | 32400 BTU/H (9500 Watts) | 460 3 Phase | 7.0 (1590 l/h) | 13.0 (50L) | 3/4" | 54.17 | 23.62 | 29.94 |
EB140WT | 47750 BTU/H (14000 Watts) | 460 3 Phase | 10.0 (2270 l/h) | 19.0 (72L) | 1" | 60.40 | 29.96 | 33.68 |
EB160WT | 54500 BTU/H (16000 Watts) | 460 3 Phase | 11.0 (2498 l/h) | 19.0 (72L) | 1" | 60.40 | 29.96 | 33.68 |
EB260WT | 89053 BTU/H (26100 Watts) | 460 3 Phase | 22.0 (4496 l/h) | 18.49 (70L) | 1-1/4" | 55.50 | 30.00 | 49.60 |
EB440WT | 151492 BTU/H (44400 Watts) | 460 3 Phase | 48.0 (10902 l/h) | 52.83 (200L) | 1-1/2" | 55.70 | 31.00 | 65.70 |
Data subject to change without notice.