94-169 CFM Filterfans PF GEN4 Series

Type 12

Features

  • Maintains a UL Tested NEMA Type 12 seal against enclosure
  • UL Recognized to UL 508A, category NITW2/8, UL File #E175229
  • Patented “Click & Fit” design provides a hardware free installation!
  • Plastic made from strong, heat resistant (ABS-FR), UL 94 VO fire approved material
  • Fan Motor is CSA Approved
  • Options: Black Grills

Accessories

Part Number Light Gray RAL7035 Part Number Black RAL9011 Voltage Power Exhaust Filter Light Gray RAL7035 Exhaust Filter Black RAL9011
PF42500T12LG PF42500T12BK 115V 20W PFA40000LG PFA40000BK
PF42500T12LG230 PF42500T12BK230 230V 18W PFA40000LG PFA40000BK
PF42500T12LG24 PF42500T12BK24 24V 5W PFA40000LG PFA40000BK
PF43000T12LG PF43000T12BK 115V 40W PFA40000LG PFA40000BK
PF43000T12LG230 PF43000T12BK230 230V 39W PFA40000LG PFA40000BK
PF43000T12LG24 PF43000T12BK24 24V 12W PFA40000LG PFA40000BK
Airflow data PF 42500 PF 43000 PFA 40000
Filter material NEMA Type 12 Filtermat NEMA Type 12 Filtermat NEMA Type 12 Filtermat
Unimpeded airflow 94 CFM 169 CFM -
Capacity free-flow 53 W/K I88 W/K -
Airflow in combination 67 CFM 142 CFM -
(Filterfan + Exhaust Filter) (PF 42500 + PFA 40000) (PF 43000 + PFA 40000) -
Capacity in combination 38 W/K 69 W/K -
(Filterfan + Exhaust Filter) (PF 43000 + PFA 40000) (PF 43000 + PFA 40000) -
Max. static pressure (Airflow = 0 m3/h) 49 Pa 112 Pa -
Filtration efficiency 0.91 0.91 0.91
Filter material grade G 4 (DIN EN 779) G 4 (DIN EN 779) G 4 (DIN EN 779)
Duty cycle 1 1 -
Technical data PF 42500 PF 43000 PFA 40000
AC/DC AC/DC
Outside dimensions in mm 252 x 252 x 97 252 x 252 x 113 252 x 252 x 38
(height x width x installation depth)
Bearing type / Lagerart ball bearings -
Fitting position / Einbaulage any, horizontal airflow preferred any
Construction housing and guard of sprayed thermoplastic, self-extinguishing, UL 94 VO
Weight 1.18 kg 1.67 kg 0.46 kg
Safety protection in accordance with DIN 31 001
Color LG RAL 7035, Light Grey
Color BK RAL9011 Black
Connections / Anschlussart cage clamp cage clamp -
Supplementary data PF 42500 PF 43000 PFA 40000
Operating temperature – 15 °C (- 5 °F) to / bis + 55 °C (+ 131 °F)
Storage temperature – 20 °C (- 4 °F) to / bis + 70 °C (+ 158 °F)
Max. relative humidity 0.9
System of protection NEMA Type 12, IP 55 (EN 60 529), when installed as specified
Basic Accessories parts kit filter mat, user manual radiant heater, fan heater, thermostat, hygrostat
Approvals UL Recognized
* Tolerance installation cutout 223 + 1/-0 thickness of material to 2 mm
224 + 1/-0 thickness of material > 2 mm < 3 mm

Need Assistance? Contact Us.