Isolation (115VAC to 115VAC) 171 Series

Plug-In

Features

  • Primary 115VAC, 50/60 Hz., Secondary 115VAC
  • Provides complete circuit isolation.
  • Electrostatic shield between primary & secondary to greatly attenuate surges and noise.
  • Hi-pot tested to 2 KV RMS.
  • Circuit breaker in primary.
  • Standard 3-wire, grounded plug & receptacle.
  • Input (primary) connected to 5 foot long cord & standard North American plug (NEMA 5-15P).
  • Output (secondary) connected to 1 foot long "pig tail" cord, 3-wire, standard North American grounded receptacle (NEMA 5-15R).
  • North American Mark of Safety - C UL & UL listed (File #E211544)
  • Indoor use only
  • Remember - These units do NOT convert line frequency

Accessories

Gallery Image

Leakage Full Load Full Load Total Surge/ Noise Capacitance Circuit
Part No. Capacity Current Efficiency Harmonic Suppression Between Windings Breaker Dimensions Weight
VA (Typ.) (Typ.) Distortion (Typ.) (Typ.) @ 1Khz (Typ.) (Amps) A B C D E Lbs
171A 100 <100 µA 89% 0.21% -37 dB 15 pF 1 3.80 5.06 4.68 3.00 3.38 6.5
171B 200 <100 µA 93% 0.195 % -37 dB 15 pF 2 3.80 5.56 4.68 3.00 3.88 8
171C 300 <100 µA 94% 0.24% -37 dB 20 pF 3 3.80 6.06 4.68 3.00 4.38 11
171E 500 <100 µA 93% 0.18% -37 dB 20 pF  5 3.80 7.06 4.68 3.00 5.38 14
171F 750 <100 µA 95% 0.24% -32 dB 20 pF  7 4.40 8.70 5.39 3.50 6.78 30
171G 1000 <100 µA 95% 0.109% -35 dB 40 pF  10 5.28 7.75 6.38 4.25 6.00 34.5

Need Assistance? Contact Us.

Data subject to change without notice.

Tags: straight isolation, circuit isolation, electrostatic, noise, surge, circuit breaker